Inspection
Inspection Details
Equipment ID
12255
12255
Inspection Date
6/15/2022
6/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25 / 20
25 / 20
External ID
60482256-2f53-4788-8736-dc6057bf31f8
60482256-2f53-4788-8736-dc6057bf31f8
Location
St. Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | Yes | No | Counterweight strikes buffer with car at top floor, has no runby. Hoist ropes need to be shortened. Reinspect within 90 days. | 10/14/2021 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 1001.2(c)(13) | No | No | Counterweight landing on buffers at top floor, hoist ropes need to be shortened. Re-inspect in 90 days 1206.8 | 12/28/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 11/21/2025 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | When the full load car safety test was performed, the car slide was 42". The maximum allowed is 28". Repair or replace car safeties to get proper slide distance. Re-inspection within 30 days required | 7/2/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 7/2/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 7/2/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 11/21/2025 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 11/21/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 11/21/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 11/21/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 3/25/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Need to test phase I and II fire service. Re-inspection required | 3/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Bottom floor hoistway door interlock cover is missing, re-install cover | 3/25/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |