Inspection
Inspection Details
Equipment ID
9663
9663
Inspection Date
6/23/2022
6/23/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
490
490
Slide
Governor Rope Pull
Door Closing Force
28/28
28/28
External ID
fddab421-aa44-467f-b225-e218fd2234d0
fddab421-aa44-467f-b225-e218fd2234d0
Location
SSM-De Paul Health Center
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6102
12255 De Paul Dr, Bridgeton, MO
Phone: (314) 344-6102
Owner
Attn: Jeff Fleming
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6456
Email: jeffrey.fleming@ssmhealth.com
SSM-De Paul Health Center
12303 De Paul Dr, Bridgeton, MO 63044
Phone: (314) 344-6456
Email: jeffrey.fleming@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | A direction indicating arrow is missing on the front opening in the car and shall be repaired | 7/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Note that the debris found in the pit appears to be biohazard material and may need to have proper protocols followed. | 7/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | A direction indicating arrow is missing on the front opening in the car and shall be repaired | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The illuminated signal marked “ELEVATOR EMERGENCY POWER” failed to activate when the elevator was placed under emergency power, repair jewel to activate as required. Reinspection required. | 5/11/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of the major alteration. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The illuminated signal marked “ELEVATOR EMERGENCY POWER” failed to activate when the elevator was placed under emergency power, repair jewel to activate as required. Reinspection required. | 9/3/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of the major alteration. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A direction indicating arrow is missing on the front opening in the car and shall be repaired. | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of the major alteration. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The illuminated signal marked “ELEVATOR EMERGENCY POWER” failed to activate when the elevator was placed under emergency power, repair jewel to activate as required. Reinspection required. | 6/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | A direction indicating arrow is missing on the front opening in the car and shall be repaired. | 3/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | No | No | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of the major alteration. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | 3/4/2026 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | Yes | Yes | Upon performing the required annual pressure test, the hydraulic cylinder of this elevator was having a significant amount of oil loss in the system. The elevator is locked out of service until the system can be repaired. | 3/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a relief valve pressure test was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. | 3/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a relief valve pressure test was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. | 3/18/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Need to replace damaged Phase I fire service keyswitch at lobby panel | 6/25/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Replace missing fire service key switch. This is a critical elevator in the surgery center. Replace key switch and re-inspect within 14 days. | 7/29/2026 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | Replace missing hoistway door safety retainers on the bottom of all hoistway doors. | 7/29/2026 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Front car door restrictor does not work, needs repaired. Re-inspection required | 7/29/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 7/29/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | When testing the elevator on emergency power, the emergency power jewel failed to illuminate, needs repaired. Re-inspection required | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Replace missing fire service key switch. This is a critical elevator in the surgery center. Replace key switch and re-inspect within 14 days. | |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | No | No | Replace missing hoistway door safety retainers on the bottom of all hoistway doors. | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Front car door restrictor does not work, needs repaired. Re-inspection required |