Inspection
Inspection Details
Equipment ID
23289
23289
Inspection Date
6/24/2022
6/24/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
24
24
External ID
b5f21d2c-9d1e-41fd-abf3-258b2981db58
b5f21d2c-9d1e-41fd-abf3-258b2981db58
Location
SSM Health Outpatient Center-St. Charles
711 Veterans Memorial Pkwy, St. Charles, MO
Phone: (000) 000-0000
Email: michelle.deckard@ssmhealth.com
711 Veterans Memorial Pkwy, St. Charles, MO
Phone: (000) 000-0000
Email: michelle.deckard@ssmhealth.com
Owner
Attn: Samantha Bley
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
Email: Samantha.Bley@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (636) 947-5369
Email: Samantha.Bley@ssmhealth.com
Billing
Attn: Michelle Deckard
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5369
Email: michelle.deckard@ssmhealth.com
SSM-St. Joseph Hospital
300 1st Capitol Dr, St. Charles, MO 63301
Phone: (636) 947-5369
Email: michelle.deckard@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator is not operating correctly. Check and repair the programming of this phone for proper operation and passenger safety. | 8/26/2019 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.12 - Car enclosure | 2.14 | The glass panel in the car enclosure does not have the ANSI Z97.1 marking visible as required by code. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | There is no fire extinguisher near the controller space, as required. Provide an ABC type extinguisher of proper size for the room. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The current state operating certificate needs to be posted near the controller space in a non-combustible frame. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.11 - Car vision panels and glass car doors | 2.14.2.5 | The glass panel in the car enclosure does not have the ANSI Z97.1 marking visible as required by code. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | There is no fire extinguisher near the controller space, as required. Provide an ABC type extinguisher of proper size for the room. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The current state operating certificate needs to be posted near the controller space in a non-combustible frame. | 9/24/2019 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.11.2.1.2(o) | x | x | The drive machine brake will not hold a car load of 125% of the rated capacity required. Repair or replacement of the brake is required and a reinspection shall be performed before the elevator can be returned to service. | 7/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | x | The testing has not been completed on the elevator at this time. The 125% weight test shall be performed before the inspection is completed. | 7/30/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | The fire tabs (Hoistway Door Safety Retainers) were not installed on the hoistway doors at the time of construction. The fire tabs shall be installed to retain the hoistway doors in the closed position if the primary means fails. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection Required. |