Inspection
Inspection Details
Equipment ID
6961
6961
Inspection Date
6/28/2022
6/28/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
079cfa32-cd06-4dde-b5ca-8018b71bdcbb
079cfa32-cd06-4dde-b5ca-8018b71bdcbb
Location
Federal Reserve Bank of St. Louis
One Federal Reserve Bank Plz, St. Louis, MO
Phone: (314) 704-7878
Alt Phone: (314) 704-7878
Email: michael.tighe@stls.frb.org
One Federal Reserve Bank Plz, St. Louis, MO
Phone: (314) 704-7878
Alt Phone: (314) 704-7878
Email: michael.tighe@stls.frb.org
Owner
Attn: Federal Reserve Bank of St. Louis
Federal Reserve Bank of St. Louis
411 Locust Street (4th and Locust Streets), SAINT LOUIS, MO 63102
Phone: (314) 444-6132
Email: bruce.c.kalmer@stls.frb.org
Federal Reserve Bank of St. Louis
411 Locust Street (4th and Locust Streets), SAINT LOUIS, MO 63102
Phone: (314) 444-6132
Email: bruce.c.kalmer@stls.frb.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. | 6/28/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | The car buffer in the elevator pit is missing the rubber striking pad. Replace the striking pad. | 8/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 8/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 8/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. | 7/19/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 as required. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | The car buffer in the elevator pit is missing the rubber striking pad. Replace the striking pad A17.1 2016 8.6.3.1 | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. | 6/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 as required. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | The car buffer in the elevator pit is missing the rubber striking pad. Replace the striking pad A17.1 2016 8.6.3.1 | 8/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The position indicating or “PI” device in the car was malfunctioning on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required. | 7/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | The car buffer rubber striking pad in the elevator pit has become dislodged. Secure the striking pad A17.1 2016 8.6.3.1 | 8/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. Electronic means has NOT been approved by the State of Missouri. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 8.11.2.1.1(n) | No | No | The ventilation fan has been replaced from the original and now has a substantial gap between the mounting. This installation does not conform to A17.1 2.14.1.6 and 8.6.2.1 as required. | 8/26/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator would not activate with the 110V disconnect in the machine room in the “off” position indicating that the battery had been depleted. Replaced the battery of this phone for proper operation and passenger safety. Reinspection required | 8/26/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The fireman’s service phase 1 and 2 shall be performed, and emergency/standby power tested before the inspection is completed. | 8/26/2026 |