Inspection
Inspection Details
Equipment ID
8920
8920
Inspection Date
6/21/2022
6/21/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
6
6
Governor Rope Pull
100 / 240
100 / 240
Door Closing Force
20
20
External ID
a9cf4f47-2f43-413a-b662-4bb5f560e303
a9cf4f47-2f43-413a-b662-4bb5f560e303
Location
Weinberg Bldg
8348 DELCREST DR, SAINT LOUIS, MO
Phone: (314) 991-2055
8348 DELCREST DR, SAINT LOUIS, MO
Phone: (314) 991-2055
Owner
Attn: Crown Center
Council Apartments II
8350 DELCREST DR, SAINT LOUIS, MO 63124
Phone: (000) 000-0000
Council Apartments II
8350 DELCREST DR, SAINT LOUIS, MO 63124
Phone: (000) 000-0000
Billing
Attn: Crown Center
Crown Center
8350 DELCREST DR, SAINT LOUIS, MO 63124
Phone: (000) 000-0000
Email: tvohsen@crowncenterstl.org
Crown Center
8350 DELCREST DR, SAINT LOUIS, MO 63124
Phone: (000) 000-0000
Email: tvohsen@crowncenterstl.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | The elevator pit light was missing a light guard on the day of inspection, reinstall light guard in the pit. | 7/5/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 7/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 6/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair the programming of this phone for proper operation and passenger safety. Reinspection required. | 6/21/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall be clean of debris | 6/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Cables shall be shortened. Car final limit was adjusted so final limit is sctivated unitl cables are shortened. Cables need to be shortened in 15 days or less. Counterweight was striking the spring buffer not allowing the final limit to stay engaged. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Procedures for inspections and tests | 2/2/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Testing of the back-up generator to run the elevators. Re-inspection required | 2/2/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pits shall be cleaned of debris | 2/2/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The emergency light does not illuminate when normal power is removed | 11/8/2024 |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | Yes | No | Platform guard no less than 48" long | 5/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test all smoke and heat detectors connected to the elevator controller. Smoke detectors, when activated shall recall elevator to primary or alternate landing. Also test phase I and 2 service key operation. Re-inspection required | 5/26/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 5/26/2026 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Provide working HVAC system in elevator machine room to keep temperature to keep elevator equipment operating range. | 5/26/2026 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | Provide governor rope data tag on governor rope | 5/26/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Provide sump pump in elevator pit. Re-inspection required | 5/26/2026 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | Provide alteration code data plate in machine room permanently marked | 5/26/2026 |
| A17.1-2016 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4 | Yes | No | Test counterweight seismic device. Re-inspection required | 5/26/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Fire service will not reset from fire service phase I to normal operation | 5/27/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Unable to complete smoke detector test due to fire service not re-setting. Re-inspection required | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Cables need to be shortened. Car final limit was adjusted so final limit is activated until cables are shortened. Counterweight was striking the spring buffer not allowing the final limit to stay engaged. Re-inspection required | 5/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need testing of backup generator to run the elevator 1 & 2. Re-inspection required | 5/27/2026 |