Inspection
Inspection Details
Equipment ID
9134
9134
Inspection Date
6/21/2022
6/21/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
73e4960f-e72c-409a-8654-974f36cf5514
73e4960f-e72c-409a-8654-974f36cf5514
Location
St. Louis University High School
4970 Oakland Ave, St. Louis, MO
Phone: (314) 531-0330
4970 Oakland Ave, St. Louis, MO
Phone: (314) 531-0330
Owner
Attn: St. Louis University High School
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: mfischer@sluh.org
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: mfischer@sluh.org
Billing
Attn: St. Louis University High School
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: jrankin@siuh.org
St. Louis University High School
4970 Oakland Ave, St. Louis, MO 63110
Phone: (314) 531-0330
Email: jrankin@siuh.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The car safeties shall be tested with a full load. | 7/29/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | The machine room floor shall cover the entire area of the machine room. Provide a cover or guard the unused machine room access opening. | 5/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting shall be not less than 10 foot-candles at the floor. | 5/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide hoist rope data tag. | 5/27/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Determine and correct cause of car not running while on car top inspection. | 7/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency telephone shall be operational. | 7/29/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current State Operating Permit shall be obtained and displayed in the Equipment Room | 6/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Fire Service must be tested and properly documented monthly on Log Sheet located in the machine room. No logs present in Machine Room | |
| A17.1-2016 : Elevators | 3.8 - Top emergency exit | 8.11.2.1.3(l) | No | No | Top emergency exit shall be properly mounted to the cartop with either hinges or a chain tethered to the cartop to prevent accidental dropping of the hatch | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Where spring buffers, elastomeric buffers, or solid bumpers are used, the bottom runby shall be not less than 150 mm (6 in.), |