Inspection
Inspection Details
Equipment ID
15707
15707
Inspection Date
10/24/2017
10/24/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
15707
15707
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
24
24
External ID
15707
15707
Location
MetroLink- 8th & Pine
323 8th St, St. Louis, MO
Phone: (314) 982-1400
323 8th St, St. Louis, MO
Phone: (314) 982-1400
Owner
Metro Accounts Payable
707 N, 1st St., St. Louis, MO 63188
707 N, 1st St., St. Louis, MO 63188
Billing
Attn: Metro Accounts Payable
P.O. Box 1349, , MO 63188
P.O. Box 1349, , MO 63188
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Need "Low Overhead" clearly posted in hoistway | 12/14/2018 | ||
conversion | conversion | n/a | Post MO State operating permit in machine room | 12/14/2018 | ||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Cab ventilation not working. | 9/30/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light not working. | 6/15/2020 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine room shall not be used for storage of non-elevator equipment. | 9/30/2020 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | AC unit cannot be located directly over the pump unit in the elevator machine room. Move AC unit | 9/8/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Condensation line cannot be mounted over the pump unit in the elevator machine room. Move line | 11/9/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.19 - Guide rails fastening and equipment | 8.11.2.1.3(y) | Slide guides on the car top have excessive play and lateral movement. Adjust, replace, or repair slide guides | 11/9/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | Repair leaking victaulic pipe fitting inside the pump unit in the maching room. | 11/9/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 8.11.2.1.5(f) | Both traveling cables are rubbing conduit in the hoistway. Move cables to prevent damage | 10/29/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Car light disconnect is located 9 feet up. Lower disconnect to where it is accessible | 11/9/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 2.8.1 | Both traveling cables are rubbing conduit in elevator hoistway. Move cables to prevent further damage | 10/29/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Air conditioning systems shall not be located directly over elevator equipment. | 9/8/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |