Inspection
Inspection Details
Equipment ID
11496
11496
Inspection Date
7/16/2018
7/16/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
340
340
Slide
Governor Rope Pull
Door Closing Force
29F/25R
29F/25R
External ID
6d4498e4-8417-4606-99fe-9d1f3a8624be
6d4498e4-8417-4606-99fe-9d1f3a8624be
Location
Glen Ridge Elementary
7447 WELLINGTON WAY, CLAYTON, MO
7447 WELLINGTON WAY, CLAYTON, MO
Owner
Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
Billing
Attn: Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Cab ceiling light diffusers are missing and shall be re-installed. | 11/11/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/27/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Articles or materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room. | 8/27/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone needs to be reprogramed to be code compliant. A two-way communications means between the car and a location staffed by authorized personnel shall be provided. | 7/21/2023 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | Yes | No | Elevator did not pass the 15 minute static test. Take corrective action as needed. Elevator turned off by maintenance company. | 7/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | There is no state operating certificate in machine room. | 9/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency lights shall be operational. | 7/22/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. | 7/22/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Non-elevator related items shall not be stored in Machine Room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Water is accumulating on the machine room floor, around pump unit . Creates a dangerous situation for working on controller |