Inspection
Inspection Details
Equipment ID
11499
11499
Inspection Date
7/17/2018
7/17/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
18F/23R
18F/23R
External ID
272f752b-ad10-4d50-bd93-dedc346bc9db
272f752b-ad10-4d50-bd93-dedc346bc9db
Location
Clayton High School
1 MARK TWAIN CIR, CLAYTON, MO
1 MARK TWAIN CIR, CLAYTON, MO
Owner
Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
Billing
Attn: Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
2 MARK TWAIN CIR, CLAYTON, MO 63105-1613
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 1/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/27/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 8/27/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | The hoistway shall be of solid construction. Patch hole in hoistway around sprinkler pipe. | 8/27/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. The certificate displayed is expired. | 11/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. | 11/1/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be functional. | 11/1/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | The auxiliary power lowering operation shall be functional. | 7/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. | 7/21/2025 |