Inspection
Inspection Details
Equipment ID
15610
15610
Inspection Date
6/28/2022
6/28/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Bradley Rasnake
Bradley Rasnake
Mechanic Name
Relief Valve Pressure
na
na
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
a3aef51e-fd45-4911-be5f-384c4ecdceab
a3aef51e-fd45-4911-be5f-384c4ecdceab
Location
Woodspring Suites
888 Arnold Commons Dr, Arnold, MO
Phone: (636) 287-6441
888 Arnold Commons Dr, Arnold, MO
Phone: (636) 287-6441
Owner
Attn: Woodspring Suites
Woodspring Suites
888 Arnold Commons Dr, Arnold, MO 63010
Phone: (636) 287-6441
Email: gm.mo433@woodspring.com
Woodspring Suites
888 Arnold Commons Dr, Arnold, MO 63010
Phone: (636) 287-6441
Email: gm.mo433@woodspring.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not call the correct elevator maintenance company. | 4/21/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The car top shall be cleaned. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | The pit shall be kept clean. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.16 - Rated load, platform area, and data plate | 8.11.2.1.1(p) | No | No | The capacity sign in the cab is illegible. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | No | No | The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Label the main electrical disconnect with the source panel and breaker. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Upper and lower hoistway access switches shall be momentary/spring return. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Upper and lower hoistway access does not stop. Adjust for code compliant stop. | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | The heat detector in the machine room shall not affect the operation of the elevator or the shunt trip since there is not a sprinkler head present. - Re-Inspection Required | 1/19/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 9/13/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light shall work. | 9/16/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 9/16/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | 6/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 6/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, appears to not have live phone line. Re-inspection required | 6/28/2022 |