Inspection
Inspection Details
Equipment ID
11723
11723
Inspection Date
6/17/2022
6/17/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
14
14
Governor Rope Pull
200 / 410
200 / 410
Door Closing Force
25
25
External ID
5b8810a8-dcfb-4d68-9666-8c46c609c32f
5b8810a8-dcfb-4d68-9666-8c46c609c32f
Location
St. Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Cab flooring is loose, protruding above car sill causing trip hazard. | 10/13/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair cab floor at opening, it is a tripping hazard | 10/13/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No ventilation in machine room. Controllers are in extreme heat, over manufacturers recommendations. 101.5b | 10/13/2022 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | Yes | Yes | The elevator safety governor was found to be worn to a degree that the activation would not set with any sort of consistency. Repair or replacement of the governor is required and a re-inspection shall be performed before the elevator can be returned to service. | 11/8/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated Missouri Operating Certificate in machine room | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean dirt, grease and debris from elevator car top | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor needs repaired. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test phase I and II fire service key. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are rouged and undersized, need to replace suspension ropes. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase II fire service operating instructions are missing inside of elevator cab, need to install correct signage | 3/25/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th and 6th floor hoistway doors, needs repaired. | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | 5/6/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase II fire service operating instructions are missing inside the elevator cab, need to install correct signage | 5/6/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)4 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired | 5/6/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 5/6/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)4 | No | No | Hoistway door non vision panels (sight guards) are missing on the bottom, 5th & 6th floor hoistway doors. Need repaired | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |