Inspection
Inspection Details
Equipment ID
11720
11720
Inspection Date
6/24/2022
6/24/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
27
27
Governor Rope Pull
300 / 800
300 / 800
Door Closing Force
25
25
External ID
96ee2506-c781-459c-b955-344c70e0d828
96ee2506-c781-459c-b955-344c70e0d828
Location
St. Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light does not work. | 9/3/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | No ventilation in machine room. Controllers under extreme heat, more than manufacturers recommendations. 101.5b | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of 8.6.The MCP shall include but not limited to examinations, tests, cleaning, lubrication, and adjustments to applicable components at regular intervals. | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Need to test phase I & II fire service. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase I fire service operating instructions are missing at the phase I fire service key switch. Need to install correct signage | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 3/25/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase I fire service operating instructions are missing at the phase I fire service key switch. Need to install correct signage | 5/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Elevator car door restrictor does not work, needs repaired. Re-inspection required | 5/11/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean oil & debris from elevator car top | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Repair machine room air conditioner, will not turn on |