Inspection
Inspection Details
Equipment ID
15341
15341
Inspection Date
7/5/2022
7/5/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
24
24
External ID
4535d681-162d-4dd0-bcbc-4639fb1e79c4
4535d681-162d-4dd0-bcbc-4639fb1e79c4
Location
Windows On Washington-IBCI Bldg
1509 Washington Ave, St. Louis, MO
Phone: (314) 283-2331
1509 Washington Ave, St. Louis, MO
Phone: (314) 283-2331
Owner
Attn: Window On Washington-IBCI Bldg
IBC Investors LLC
PO Box 5005, Cahokia, IL 62206
Phone: (000) 000-0000
IBC Investors LLC
PO Box 5005, Cahokia, IL 62206
Phone: (000) 000-0000
Billing
Attn: Donny Choate
IBC Investors LLC
189 American Grain St, Cahokia, IL 62206
Phone: (000) 000-0000
IBC Investors LLC
189 American Grain St, Cahokia, IL 62206
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.6.4.12 | Yes | No | Remote governor trip not functioning. | 11/30/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 9/10/2024 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 testing of the car safeties. Record slide. Check rails for dressing. | 9/10/2024 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed several bottom door guides (on different floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2 through 2.27.8 Firefighter Service | Yes | Yes | On Phase II operations, door close function not working. Car removed from service. | 9/10/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 4/7/2026 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 5 safety test, record slide. | 4/7/2026 |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | No | No | Observed bottom door guides ( on several floors) don’t have fire tabs bent down, make so. | 4/7/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 4/7/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean upper and lower pits. | 4/7/2026 |