Inspection
Inspection Details
Equipment ID
11137
11137
Inspection Date
6/28/2022
6/28/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
715
715
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
9dd505ba-da37-4217-848e-326bf347c7f1
9dd505ba-da37-4217-848e-326bf347c7f1
Location
MO Baptist University - Chapel Fine Arts
2 College Park Dr, Creve Coeur, MO
Phone: (314) 434-1115
2 College Park Dr, Creve Coeur, MO
Phone: (314) 434-1115
Owner
Attn: MO Baptist University
MO Baptist University
1 College Park Dr, St. Louis, MO 63141
Phone: (314) 744-7623
Email: john.shaw@mobap.edu
MO Baptist University
1 College Park Dr, St. Louis, MO 63141
Phone: (314) 744-7623
Email: john.shaw@mobap.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | No | Provide the code correct Phase 1 fire service signage in the lobby. | 5/30/2019 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | No | Replace Phase 1 key switch bezel that is unreadable. | 5/30/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/15/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | The illegible phase 1 firefighters operation key switch bezel shall be replaced. | 10/15/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/28/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/29/2023 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/14/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 8/29/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power and give proper location. | 9/13/2023 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | There is no MCP present in machine room. | 9/1/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 9/26/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Standing water in pit needs to be removed. | 10/8/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 10/8/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | Emergency communications/phone not working. Elevator red tagged out of service. | 10/8/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Standing water in pit needs to be removed. Existing self-certify violation not checked at time of phone re-inspect. Violation to be certified as corrected by owner. | 11/6/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Existing self-certify violation not checked at time of phone re-inspect. Violation to be certified as corrected by owner. | 11/6/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The phone shall establish 2-way communication and give location of the elevator on battery back up. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | The pit shall be kept clean and dry. | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the machine room. |