Inspection
Inspection Details
Equipment ID
10255
10255
Inspection Date
7/8/2022
7/8/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
f6267734-a055-43fd-971f-086667c401a4
f6267734-a055-43fd-971f-086667c401a4
Location
Metropolitan Square
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
211 N Broadway, St. Louis, MO
Phone: (314) 436-1212
Owner
Attn: Metropolitan Square LLC
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (000) 000-0000
Metropolitan Square LLC
211 N Broadway, St. Louis, MO 63102
Phone: (000) 000-0000
Billing
Attn: Jones Lang LaSalle
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: etcollett@metrostlouis.org
Jones Lang LaSalle
211 N Broadway, Ste 1290, St. Louis, MO 63102
Phone: (314) 982-1400 Ext: 4662
Email: etcollett@metrostlouis.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Suspension ropes are below minimum diameter. Replace within 30 days. | 11/11/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is not working. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform 125% brake test. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform full load buffer test for car & counterweight. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform full load safety set. Re-inspection required | 7/8/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to test spin governor. Re-inspection required | 7/8/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency power operation needs to be tested | 12/7/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Repair inoperative Phase l fire recall visiual indicator | 12/7/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Repair lights above hoist machine to provide required illumination | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair inoperative emergency Lights | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Replace broken shackel springs on car and counterweight ends | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.2.5 Rope Tension (Re-Inspect) | Yes | No | Replase missmatched shackle spring on counterweight | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace defective right top post roller on counterweights | 8/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Elevator cab emergency lights do not work, need repaired. Re-inspection required | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Suspension ropes have broken shackle springs on the car & counterweights, need to replace shackle springs | 8/12/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required | 8/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone shall be operational | 8/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine to Motor coupling bushings are deteriorated and shall be replaced. | 8/15/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency Power and Fire Service shall be tested | 8/15/2026 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Hoist ropes have broke lays in all 4 ropes in multiple sections. Hoist ropes shall be replaced. | 8/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine bed plate isolations pads are deteriorated and shall be replaced. | 8/15/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine bed plate isolations pads are deteriorated and shall be replaced. | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | Yes | Hoist ropes have broke lays in all 4 ropes in multiple sections. Hoist ropes shall be replaced. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Machine to Motor coupling bushings are deteriorated and shall be replaced. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone shall be operational |