Inspection
Inspection Details
Equipment ID
1477
1477
Inspection Date
8/31/2018
8/31/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
79284e4a-2637-49bf-b16d-0864e19eb5bf
79284e4a-2637-49bf-b16d-0864e19eb5bf
Location
Macy's Midwest
49 CHESTERFIELD MALL, CHESTERFIELD, MO
49 CHESTERFIELD MALL, CHESTERFIELD, MO
Owner
Macy's
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
Billing
Attn: Macy's
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
7 W 7TH ST 19TH FL, CINCINNATI, OH 45202-2424
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current State certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Replace right handrail cracked) | |
| MO Minimum : Elevators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 | No | No | Provide copies of step indexing reports to finalize inspection | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pits | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Replace right handrail(cracked) this was a violation from last years inspection no action taken | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | step indexing failed needs to be corrected then retested | 7/12/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Need a maintenance control program posted on controller on or by next test | |
| Missouri Minimum : Escalators | CSR 40-5.100 State Operating Certificate | 5.100(2) display of certificate | No | No | Post current state certificate in machine room | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.1 Escalator Handrails | No | No | Replace right handrail (cracking) |