Inspection
Inspection Details
Equipment ID
9862
9862
Inspection Date
6/27/2022
6/27/2022
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
James Suedkamp
James Suedkamp
Relief Valve Pressure
Slide
C: 39", CW: 16"
C: 39", CW: 16"
Governor Rope Pull
C: 350/700, CW:330/650
C: 350/700, CW:330/650
Door Closing Force
23
23
External ID
f7862511-535b-4e9c-b0ba-048f942ce2d6
f7862511-535b-4e9c-b0ba-048f942ce2d6
Location
One Financial Plaza
501 N Broadway, St. Louis, MO
Phone: (314) 588-7171
Email: foxr@stifel.com
501 N Broadway, St. Louis, MO
Phone: (314) 588-7171
Email: foxr@stifel.com
Owner
Attn: One Financial Plaza/Cushman & Wakefield
One Financial Plaza/Cushman & Wakefield
501 N Broadway, Ste 150, St. Louis, MO 63102
Phone: (314) 588-7171
Email: Aly.Kasten@cushwake.com
One Financial Plaza/Cushman & Wakefield
501 N Broadway, Ste 150, St. Louis, MO 63102
Phone: (314) 588-7171
Email: Aly.Kasten@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | No | No | Replace bottom left counterweight roller guides. | 2/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher is out of date. | 2/20/2020 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Rope gauge bottoms on #5 hoist rope between floors 10-11. Replace hoist ropes within 60 days from above date. | 8/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace deteriorating under car safety assembly bushings. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Counterweight safety tension sheave nearing bottom of travel, raise sheave. | 1/9/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace first floor interlock box cover. | 1/9/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Provide data tag for recent suspension rope replacement on machine room hitch plate. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace under car safety assembly bushings. | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 2/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 4/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 4/1/2026 |