Inspection
Inspection Details
Equipment ID
20733
20733
Inspection Date
7/8/2022
7/8/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
590
590
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
c22fc85d-1227-4bdf-9582-2ac52bebb36a
c22fc85d-1227-4bdf-9582-2ac52bebb36a
Location
O'Fallon Park Rex Plex
4343 W FLORISSANT AVE, SAINT LOUIS, MO
Phone: (314) 531-0505
4343 W FLORISSANT AVE, SAINT LOUIS, MO
Phone: (314) 531-0505
Owner
Attn: Rob West
O'Fallon Park Rex Plex
4343 W Florissant Ave, St. Louis, MO 63115
Phone: (314) 932-1423
Email: rob.west@gwrymca.org
O'Fallon Park Rex Plex
4343 W Florissant Ave, St. Louis, MO 63115
Phone: (314) 932-1423
Email: rob.west@gwrymca.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.2.1 | No | No | Only machinery and equipment used in conjunction with the function or use of the elevator shall be permitted in the elevator machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | The light switch in the machine room shall be manual ON/OFF. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | The minimum illumination at the car threshold, with the door closed, shall be not less than 5 foot-candles for passenger elevators. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve shall be constructed, installed, and adjusted to ensure the tripping speed shall be not less than 110% nor greater than 140% of the elevator operating speed in the down direction, but in no case shall exceed 60 ft/min above the rated elevator speed. Elevator taken out of service by maintenance company. | 8/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Non-elevator related items shall not be stored in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | The light switch in the machine room shall be manual ON/OFF. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking. Door drags and jams, preventing full open and self close. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service shall be tested monthly and documented in the fire service testing log as required. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit light shall work. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment room in a non-combustible frame with a clear protective plate over it. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed and the date shall be avaliable on-site. |