Inspection
Inspection Details
Equipment ID
10430
10430
Inspection Date
7/25/2022
7/25/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
310
310
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
71389315-9936-4364-8377-7036f89def74
71389315-9936-4364-8377-7036f89def74
Location
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
Owner
Attn: John Dontrich
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The elevator car door restrictor did not operate when tested. The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/22/2018 |
| conversion | conversion | n/a | No | No | A Victaulic fitting is noticeably leaking oil in the hoistway. Repair the fitting with an adequately sized valve. | 10/20/2020 |
| conversion | conversion | n/a | No | No | There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The elevator car door restrictor did not operate when tested. The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | A Victaulic fitting is noticeably leaking oil in the hoistway. Repair the fitting with an adequately sized valve. | 10/20/2020 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 | No | No | The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. | 10/20/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The oil cooling unit did not operate when activated on the day of inspection. Repair the cooling unit to operate as designed. | 10/20/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted:The visual signal device did not light in the car when phase I was activated. Reinspection is required. | 3/24/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 8/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator testing and fire service shall be tested. Scheduled on 8/19/25 | 8/19/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 2/24/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 2/24/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. This is the 3rd consecutive year that this violation has been issued. Corrections SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance, |