Inspection
Inspection Details
Equipment ID
7464
7464
Inspection Date
8/23/2018
8/23/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
320
320
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
ca9e70b3-c7dc-4520-b938-44c3de91e1f2
ca9e70b3-c7dc-4520-b938-44c3de91e1f2
Location
Holiday Inn / St. Louis Airport
4505 WOODSON RD, SAINT LOUIS, MO
4505 WOODSON RD, SAINT LOUIS, MO
Owner
Attn: Holiday Inn Airport
McMahon Family LP
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
McMahon Family LP
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Billing
Attn: McMahon Family LP
Holiday Inn Airport
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Holiday Inn Airport
4505 WOODSON RD, SAINT LOUIS, MO 63134-3703
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | On Phase 1 and 2 fire service, car door re-opening device (light ray) is not overridden. Light ray shall be overridden on fire service. | 11/4/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Phase I operating procedures need to be posted near key switch in lobby. | 5/28/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase II operation failed. Repair and retest by 6/16/20 or unit will be red tagged and removed from service. | 3/9/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Remove all non-elevator related equipment from elevator machine room. | 5/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Provide cover for bulbs in car. | 5/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top | 5/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide updated fire extinguisher in machine room. | 5/28/2025 |
| MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)1 | No | No | Return line to tank is constantly dripping. Replace packing. | 5/28/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase I (in car) visual indicator does not work. | 3/9/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 5/28/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Light ray is not overridden in Phase I. Repair & re-inspect in 15 days | 9/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Repair 3rd floor button, relay is mechanically blocked | 5/28/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | Car shall have a visual light that works on Phase I. Re-inspection required | 9/19/2022 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing alarm bell to work (also check on 110v. disconnect off). | 9/20/2024 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing alarm bell to work. | 11/21/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Tighten car hand rails as needed. | 5/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Top of car light not working, make so. | 5/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell is not working. Re-inspection required | 1/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Provide existing top of car light to work | 5/28/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car handrails are loose, need to be tighten as needed | 5/28/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be clean and dry | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | Yes | No | Machine room ceiling is leaking water onto emergency lowering equipment. Re-inspection required |