Inspection
Inspection Details
Equipment ID
26037
26037
Inspection Date
7/26/2022
7/26/2022
Inspection Type
Initial Inspection
Initial Inspection
Inspector Name
F. Scott Gibson
F. Scott Gibson
Mechanic Name
Henry Steverson
Henry Steverson
Relief Valve Pressure
n/a
n/a
Slide
Instantaneous
Instantaneous
Governor Rope Pull
N/A
N/A
Door Closing Force
N/a
N/a
External ID
82def744-19e9-4bb1-b1f0-80b46cdee548
82def744-19e9-4bb1-b1f0-80b46cdee548
Location
JBS
22701 N March Rd, Centralia, MO
Phone: (573) 682-5584
22701 N March Rd, Centralia, MO
Phone: (573) 682-5584
Owner
Attn: JBS
JBS
1770 Promontory Circle, Greeley, CO 80634
Phone: (000) 000-0000
JBS
1770 Promontory Circle, Greeley, CO 80634
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 4.4 - Hoistway door locking devices | 2.12.2.5 | Yes | Yes | Elevator Retiring Cam Device Failed, the Electrical Operational Contacts required by the Cam to operate had been jumped out. Red Tag was required per A17.1 2016 8.10.1.4. | 10/24/2022 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | No | No | Access to pit requires a pit ladder, pit depth is 45 inches per 2.2.4.2 pit greater than 35 inches requires pit ladder. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | No | No | A permanent lighting fixture shall be provided in compliance with 2.2.5.1-2.2.5.3. Note: Existing Electrical Devices are in Explosion Proof Flex & Conduit. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.3 | Yes | No | Pit Construction A17.1 2.2.2.3 requires a permanent provision to prevent accurance of ground water in the pit. | 10/24/2022 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | A17.1 Section 2.4 item 2.4.2.2 requires a min counterweight runby of 9 inches for elevators with spring buffers which operate at 100 fpm. Hoist ropes require shortening. | 10/24/2022 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 2.12.6 | Yes | No | A17.1 Section 2.12.6.1 Access to Hoist way for Emergency purposes shall be at all landings A17.1- 5.7.8.3 requires Access points minimum at Bottome l & Top Landings. Presently there are no access provisions at any landings. | 10/24/2022 |
| A17.1-2016 : Elevators | 3.1 - Top-of-car stop switch | 2.26.2.8 | Yes | No | Stop Switch on Top of Car shall be provided conforming to 2.26.2.5(a)(b) and (c). | 10/24/2022 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8 | Yes | No | 8.10.2.2.2(g) Inspection and Testing panel per 2.26.4.1(d) the Elevator Car Safety Circuit contact points for testing have not been brought to the Controller test points to verify contact devices. The point of verification has not been identified in Controller. | 10/24/2022 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | A17.1 2.7.9.1 Permanently installed electric Lighting shall be provided in all Machine Spaces, Illumination shall not be less than 19(fc). A light switch shall b e provided at entry level. | 10/24/2022 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | Yes | No | A17.1 Section 8.9.1 An Individual Data Tag shall be provided and maintained for each unit. | 10/24/2022 |