Inspection
Inspection Details
Equipment ID
8272
8272
Inspection Date
7/29/2022
7/29/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
500/480
500/480
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
460d34b2-f3e8-48e1-93c0-7f94f119c90d
460d34b2-f3e8-48e1-93c0-7f94f119c90d
Location
America's Center
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
Owner
Attn: America's Center
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Clean oil and oil dry off pit floor | |||
| conversion | conversion | n/a | Alarm bell inoperative need repair | |||
| conversion | conversion | n/a | Reduce door closing force pressure, both sides | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit shall be kept clean and dry. Clean oil and dry pit. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | Method of oil collection shall not exceed 5 gal. Repair leaking cylinder head seal. Scavenger pump is for temp use leak is fixed. | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.8 - Door closing force | 2.13.4.2.3 | x | x | Door closing force on both doors exceeds maximum, adjust to correct setting and reinspect upon repair. | 11/23/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide written maintenance control program to be kept on site. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | x | Unit not working | 7/29/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | x | A copy of the MCP shall be kept in the machine room for each elevator | 7/29/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Piston packing worn and leaking, repair as needed. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current certificate. | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Pit has significant amount of oil in it, remove. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | Sump pump in the pit is under oil, replace if needed. | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Phone in car not working correctly. | 12/7/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide MCP. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV needs to be tested in 90 days or less. Re-inspection required | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current operating certificate shall be displayed in the machine room | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | Replace worn cylinder packing rings to reduce leakage | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Clean pit to remove debris, water and/or oil and address sources | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Sump pump under oil, replace if needed | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Car emergency signal failed Cat 1 Emergency Communications test. Re-inspection required | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Need to provide a MCP |