Inspection
Inspection Details
Equipment ID
20617
20617
Inspection Date
7/29/2022
7/29/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
See report
See report
Slide
Governor Rope Pull
Door Closing Force
See report
See report
External ID
3ea6f3d1-b1e7-487b-b6bb-6acc8546211e
3ea6f3d1-b1e7-487b-b6bb-6acc8546211e
Location
America's Center
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
701 Convention Plz, St. Louis, MO
Phone: (314) 342-5036
Owner
Attn: America's Center
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger line from pit | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Bottom of car buffer striking plates have come loose and fallen off, replace as needed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Phone not working | 7/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lights not working,bell ok. | 7/29/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP | |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Pull strap at 3rd floor missing | |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Pull strap on 1st floor door broken,replace. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit stopped working, no testing performed. | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | 2 car buffer striking plates have fallen off, need to be re-installed | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing procedures. Re-inspection required | |
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | No | No | Replace broken straps on hall doors | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required |