Inspection
Inspection Details
Equipment ID
10424
10424
Inspection Date
8/1/2022
8/1/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
10
10
Governor Rope Pull
60/500
60/500
Door Closing Force
20
20
External ID
265bc518-cfc6-4740-aeba-5ce29b73447d
265bc518-cfc6-4740-aeba-5ce29b73447d
Location
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
Owner
Attn: John Dontrich
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone door cabinet handle is missing. The handle shall be repaired to operate. | 12/23/2019 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | The elevator car safeties failed to apply when the governor was mechanically set. The elevator was tagged out of service and the power disconnected. The elevator shall be repaired and a reinspection shall be performed before the elevator is returned to service. | 12/23/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The visual signal device did not light in the car when phase I was activated. | 12/23/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 10/20/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The visual signal device did not light in the car when phase I was activated. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 8/10/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 11/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The ventilation cooling fan in the controller shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed. | 11/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The hoistway door at the 7th landing is not self-closing/self-locking. The hoistway door shall be adjusted. | 8/16/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel. | 11/22/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator and fire service testing shall be done. Scheduled 8/19/25 | 8/19/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | emergency two way communication device is inoperable | 8/19/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way communication device is inoperable. Re-inspection required |