Inspection
Inspection Details
Equipment ID
22061
22061
Inspection Date
8/4/2022
8/4/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
21
21
External ID
78b2e2ec-f2a5-47ca-b8fd-a020aff92d86
78b2e2ec-f2a5-47ca-b8fd-a020aff92d86
Location
Blair School Apts
2707 Rauschenbach Ave, St. Louis, MO
Phone: (314) 899-9762
2707 Rauschenbach Ave, St. Louis, MO
Phone: (314) 899-9762
Owner
Attn: Colleta Parker
New Blair School LP
261 Gorham Rd, south Portlan, ME 04106
Phone: (769) 798-8321
New Blair School LP
261 Gorham Rd, south Portlan, ME 04106
Phone: (769) 798-8321
Billing
Attn: Colleta Parker
Arcway Common Apts
2707 Raushenback Ave, St Louis, MO 63106
Phone: (314) 899-9762
Email: colleta.parker@presmgmt.com
Arcway Common Apts
2707 Raushenback Ave, St Louis, MO 63106
Phone: (314) 899-9762
Email: colleta.parker@presmgmt.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Phase 1 and Pase 2 fire service did ot operate correctly | 8/20/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 12/11/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | The machine space lighting was not operational on the day of inspection. Repair lighting for proper illumination for maintenance and emergency personnel. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.11.2.1.4(b) | Yes | No | The hoistway door tension on the lower landing shall be repaired to self-close. | 8/4/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 8/26/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The elevator pit shall be cleaned of dust and debris. | 8/26/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Flexible conduit in hoistway needs to be fastened to hoistway ceiling | 5/14/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean pit | 5/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Lighting in hoistway overhead machine space shall work | 5/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | It appears the governor rope needs to be shortened as the governor tail sheave is at or nearing its full travel. | 8/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Provide code compliant runby. | 8/12/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service testing shall be performed and documented monthly. | 9/23/2025 |