Inspection
Inspection Details
Equipment ID
10425
10425
Inspection Date
8/3/2022
8/3/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
100/450
100/450
Door Closing Force
16
16
External ID
3f479cf0-2320-4487-9e17-5afe23dee456
3f479cf0-2320-4487-9e17-5afe23dee456
Location
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
10010 Kennerly Rd, St. Louis, MO
Phone: (314) 525-1084
Alt Phone: (314) 703-0773
Fax: (314) 525-1569
Email: robert.hicks@mercy.net
Owner
Attn: John Dontrich
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Mercy Hospital South
10010 Kennerly Rd, St. Louis, MO 63128
Phone: (314) 525-1194
Alt Phone: (314) 541-5005
Fax: (314) 525-1569
Email: john.dontrich@mercy.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | The elevator car safety operating switch is not performing as it was designed. The switch is a selfresetting switch that is designed to activate when the car safeties are set and then resets when they are released. At this time, the switch has to be manually reset when the safeties are released. Repair or replace the safety operated switch to activate as designed. A reinspection is required for this. | 8/16/2018 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | The elevator pit shall be cleaned of dust and debris. | 7/29/2019 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | The elevator car safety operating switch is not performing as it was designed. The switch is a self-resetting switch that is designed to activate when the car safeties are set and then resets when they are released. At this time, the switch has to be manually reset when the safeties are released. Repair or replace the safety operated switch to activate as designed. A reinspection is required for this. | 7/29/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The emergency light fixture inside the elevator is not operational and shall be repaired. | 10/20/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 10/20/2020 |
| A17.1-1996 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 1001.2(e)(10) | Yes | Yes | The elevator car safety operating switch is not performing as it was designed. The switch is a self-resetting switch that is designed to activate when the car safeties are set and then resets when they are released. At this time, the switch has to be manually reset when the safeties are released. Replace the safety operated switch to activate as designed. A reinspection is required for this. | 8/21/2020 |
| A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | No | No | A17.1 2016 8.6.2.1 The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | 10/20/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 10/20/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 11/22/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair this phone for proper operation and passenger safety. Reinspection required. | 3/24/2023 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| A17.1-1996 : Elevators | 3.18 - Car frame and stiles | 203 | No | No | The top guide shoe on the elevator car is worn and shall be replaced. | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A grease seal on the drive machine is leaking excessively and shall be replaced. | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The electrical box cover for the tape reading device on top of the car has been removed and shall be reinstalled. | 7/23/2026 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | No | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. | 7/23/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A grease seal on the drive machine is leaking excessively and shall be replaced. | 7/23/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator and fire service testing shall be done. Scheduled 8/19/25 | 8/19/2025 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 101.5b | Yes | No | The ventilation in the machine room is marginally efficient to keep the elevator controller at its required temperature for operation. At this time, the elevator maintenance contractor has the elevator controller doors open with a small ventilation fan keeping the operating temperature sufficient for the elevator controller, which does not meet the code requirement. Upgrade the elevator machine room ventilation. This is the 4th year that this violation has been issued. A permanent means SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance. |