Inspection
Inspection Details
Equipment ID
2045
2045
Inspection Date
8/11/2022
8/11/2022
Inspection Type
Alteration
Alteration
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Wesley Cook
Wesley Cook
Relief Valve Pressure
260
260
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
44ff4a7b-4a5b-4e4e-bd4c-7af30d6f9693
44ff4a7b-4a5b-4e4e-bd4c-7af30d6f9693
Location
Lee's Summit High School
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
400 SE Blue Pkwy, Lee's Summit, MO
Phone: (816) 986-2000
Email: matthew.tillman@lsr7.net
Owner
Attn: Lee's Summit R-7 School District
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | x | Emergency phone dropping call after connection. | 1/19/2021 | |
MO Minimum : Elevators | (S) - Fire Service | (S)1 | x | x | Fire service works, but won't reset with the key after testing. | 1/19/2021 |
MO Minimum : Elevators | (I) - Pits | (I)7 | Pit switch working, but incorrectly labeled. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Fire service testing log not up to date. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)2 Alterations | Fire sprinkler added in machine room during remodeling work. Remove, or provide a shunt trip device and heat detector in machine room. | |||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | x | Sprinkler line for shunt trip not finished. | 1/18/2023 | |
A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. Line? | 4/1/2024 | |
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Shunt trip not overriding battery lowering. Needs relay added | 4/1/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | x | Top of hoistway smoke sensor recalls elevator to wrong floor. Relay needed | 4/1/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Machine room needs 110v receptical | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. Bldg line. | 2/20/2024 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | Machine room needs 110v gfci outlet | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. | 8/27/2024 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working, alarm bell ok. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Jack packing leaking, causing pit jug to overflow. |