Inspection
Inspection Details
Equipment ID
6425
6425
Inspection Date
8/31/2022
8/31/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19
19
External ID
f6e21a64-a151-4c1b-b790-fd1c084c44ca
f6e21a64-a151-4c1b-b790-fd1c084c44ca
Location
Bonhomme Place
7700 Bonhomme Ave, Clayton, MO
Phone: (314) 336-2365
7700 Bonhomme Ave, Clayton, MO
Phone: (314) 336-2365
Owner
Attn: J.S. CRE Bonhomme, LLC
J.S. CRE Bonhomme, LLC
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 655-5824
Alt Phone: (314) 899-5030
Email: Carol.Crawford@cbre.com
J.S. CRE Bonhomme, LLC
1807 Park 270 Dr, Ste 465, St. Louis, MO 63146
Phone: (314) 655-5824
Alt Phone: (314) 899-5030
Email: Carol.Crawford@cbre.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Replace selector cable (red rouge) | 3/16/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide monthly fir service test with documentation on log in machine room | 3/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need maintenance control program on site posted on controller | 10/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Yes | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 5/25/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Yes | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 5/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Where elevator equipment is located or its enclosure is configured such that application of water from sprinklers could cause unsafe elevator operation, means shall be provided to automatically disconnect the main line power supply to the affected elevator and any other power supplies used to move the elevator upon or prior to the application of water. | 5/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency/standby power operation of the elevator shall be tested. | 5/25/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | All live parts of electrical apparatus in the hoistway and the machine room shall be enclosed. | 5/25/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | Yes | No | Lighting in the machine room shall be not less than ten (10) foot-candles at floor level. | 5/25/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Firefighters emergency operation shall apply to all automatic elevators. Fire service is not operational. All phases of fire service and initiating devices shall be tested. | 5/25/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 4/24/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 4/24/2023 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(d)(1) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 4/24/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency power. Elevator did not work per code requirements. | 4/24/2023 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/24/2023 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | The hoist ropes have stretched and the counterweight is compressing the buffer. | 4/24/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The car emergency signal device (bell) did not work. | 4/24/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Up to date operating certificate required in the elevator machine room. | 6/24/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation of the elevator shall be tested. | 5/24/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/10/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 6/10/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be operational. | 5/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need all CAT5 components of testing. | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) | Yes | No | Phase I Recall illuminated Fire Hat at Main landing is not working. | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The emergency stop switch in the car shall not be made ineffective on Phase I emergency Recall Operation. | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist Ropes appear dry and severely "dusting". Ropes shall be cleaned and lubricated per OEM recommendations | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Adjust upthrust roller bearings for proper clearance to door hanger track such that the door-to-door gap at the bottom is less than 1".(All floors) | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris and fan. | 5/11/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.5 Phase 1 Visual Signal (Re-Inspection) | Yes | No | Phase I Recall illuminated Fire Hat at Main landing is not working. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(c) Stop Switch Inoperable in Fire Service (Re-Inspection) | Yes | No | The emergency stop switch in the car shall not be made ineffective on Phase I emergency Recall Operation. | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | Yes | No | Hoist Ropes appear dry and severely "dusting". Ropes shall be cleaned and lubricated per OEM recommendations | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Adjust upthrust roller bearings for proper clearance to door hanger track such that the door-to-door gap at the bottom is less than 1".(All floors) | 5/29/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris and fan. | 5/29/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need all CAT5 components of testing except governor info above. | 5/29/2026 |