Inspection
Inspection Details
Equipment ID
19743
19743
Inspection Date
8/10/2022
8/10/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Harris
David Harris
Mechanic Name
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
22
22
External ID
560d55b0-608c-480b-90e9-452874989dc7
560d55b0-608c-480b-90e9-452874989dc7
Location
Camden on the Lake
2359 BITTERSWEET RD, LAKE OZARK, MO
Phone: (573) 365-5620
2359 BITTERSWEET RD, LAKE OZARK, MO
Phone: (573) 365-5620
Owner
Camden on the Lake
2359 BITTERSWEET RD, LAKE OZARK, MO 65049-7008
2359 BITTERSWEET RD, LAKE OZARK, MO 65049-7008
Billing
Attn: Camden on the Lake
2359 BITTERSWEET RD, LAKE OZARK, MO 65049-7008
2359 BITTERSWEET RD, LAKE OZARK, MO 65049-7008
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 8/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Inspection incomplete - Elevator was left shut down due to software issues and bad card. Fire service still needs to be tested as well as the entire category 5 test. | 11/8/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine room lights all shall work and have 10 fc of light. | 11/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | A17.1S - 2005 - 2.7.9.1 - Machine/control spaces or rooms lighting need to be at least 19fc at the floor level. (Previously incorrectly cited as 10fc). Note: This unit is an MRL | 11/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | A17.1S - 2005 - This unit is an MRL and there is no GFI receptacle or lights in overhead which is a machine space. | 11/6/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | Yes | No | - This unit is an MRL and there is no GFI receptacle or lights in overhead which is a machine space. This was uncorrected from last year | 8/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door not self locking | 11/6/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone Does not work | 8/19/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | This unit is an MRL and there is no GFI receptacle or lights in overhead which is a machine space. | 11/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | repair/shorten runby | 8/27/2026 |