Inspection
Inspection Details
Equipment ID
14499
14499
Inspection Date
8/8/2022
8/8/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
290
290
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
4e1baac4-95e3-40cc-9f0d-c434b5810369
4e1baac4-95e3-40cc-9f0d-c434b5810369
Location
Terra Cotta Parking Garage
410 N 16th St, St. Louis, MO
Phone: (314) 621-6750
410 N 16th St, St. Louis, MO
Phone: (314) 621-6750
Owner
Attn: Jessie Blaha-Reid
Terra Cotta Garage c/o Sentry Management
9666 Olive Blvd, Ste 116, Saint Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Terra Cotta Garage c/o Sentry Management
9666 Olive Blvd, Ste 116, Saint Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | clean elevator pit | 9/21/2019 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 8/16/2019 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Remove water and oil from pit. | 1/28/2021 | ||
A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | x | The door closing force shall not exceed 30 lbs. | 10/12/2021 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit shall be kept clean. | 11/29/2023 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/29/2023 | ||
A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | x | The door closing pressure still exceeds 30 lbs. The door is timing out and stalling. Take corrective action as needed. | 11/29/2021 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | x | Remove all non elevator related items from machine room. Re-inspection required | 5/5/2023 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of current state operating certificate needs to be properly displayed in machine room | 11/29/2023 | ||
MO Minimum : Elevators | (I) - Pits | (I)1 | Pit needs to be cleaned | 11/29/2023 | ||
MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | pit light shall work | 11/29/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | A written Maintenance control program shall be kept on site for each elevator | 11/29/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Cartop light bulb is burned out. replace same | 11/29/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency light and alarm shall work | 8/4/2023 | |
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Elevator machine room is not to be used for storage of non elevator related materials and equipment. Remove same | 11/29/2023 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Repair fire service phase 2 key switch. Not Red Tagged. 14 days to correct violation. | 12/20/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Fire service phase 2 operation shall be tested. | 12/20/2024 | |
A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2c (Clean Car Tops) | Clean cartop. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | Fire service testing shall be documented monthly. | |||
MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | New fire alarm panel in the machine room is not allowed. Either relocate outside of the room or state variance from elevator board shall be applied to allow installation. |