Inspection
Inspection Details
Equipment ID
23746
23746
Inspection Date
7/28/2022
7/28/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
William Keeton
William Keeton
Mechanic Name
Brent Davis
Brent Davis
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23F/18R
23F/18R
External ID
54c3ae3e-0261-4016-bc1d-c4c44e91fa61
54c3ae3e-0261-4016-bc1d-c4c44e91fa61
Location
Wexford Science & Technology
4220 DUNCAN AVE, SAINT LOUIS, MO
Phone: (314) 779-7906
4220 DUNCAN AVE, SAINT LOUIS, MO
Phone: (314) 779-7906
Owner
Attn: Heather Beaven
Wexford Science & Technology
1090 King Georges Post Rd, Ste 505, Edison, NJ 88373
Phone: (000) 000-0000
Email: beaven@cic.com
Wexford Science & Technology
1090 King Georges Post Rd, Ste 505, Edison, NJ 88373
Phone: (000) 000-0000
Email: beaven@cic.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 7/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency/standby power operation of the elevator shall be operational. | 7/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 2.18.7 | Yes | No | Subsequent to the first stop of the car following the opening of the tail sheave tension switch, the car shall remain inoperative until the switch is manually reset. Note: Currently this switch opens the safety circuit, stopping the car immediately. | 8/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power operation of the elevator must be tested annually. | 11/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service testing must be documented monthly. | 8/27/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hoist rope tail retaining clips shall be properly spaced. | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris and rail oil puddles. | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Rope data tag missing on hoist ropes. Need replacement. | 1/15/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2-WAY COMMUNICATION DEVICE SHALL WORK AS DESIGNED. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.7.2.21 | Yes | No | Suspension means shall be replaced due to rouge and reduced diameter( 1of6 ropes = "NO GO" on gauge) . |