Inspection
Inspection Details
Equipment ID
9856
9856
Inspection Date
8/28/2018
8/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
135ac2bd-596e-437d-b6a8-3da9d0362558
135ac2bd-596e-437d-b6a8-3da9d0362558
Location
One Financial Plaza
501 N BROADWAY, SAINT LOUIS, MO
501 N BROADWAY, SAINT LOUIS, MO
Owner
West Park II LLC c/o Cushman & Wakefield
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102-2121
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102-2121
Billing
Attn: West Park II LLC c/o Cushman & Wakefield
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102-2121
501 N BROADWAY STE 150, SAINT LOUIS, MO 63102-2121
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Cab alarm bell is inoperative on normal and back-up modes. | 3/6/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | Upper final limit switch roller deterioration noticed, replace. | 7/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Raise counterweight governor tail sheave. | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually. | 2/8/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 2/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The OTIS MCP and documentation for 2021, 2022 & 2023 are missing. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. | 10/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Communication loss monitor operation shall be tested. | 10/15/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be performed monthly | 4/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 4/1/2026 |