Inspection
Inspection Details
Equipment ID
25581
25581
Inspection Date
7/13/2022
7/13/2022
Inspection Type
New Installation
New Installation
Inspector Name
Sean McLaughlin
Sean McLaughlin
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
Slide
12
12
Governor Rope Pull
24/205
24/205
Door Closing Force
23
23
External ID
13c1b3e0-e335-4d87-a3cc-9b0f7350b2f3
13c1b3e0-e335-4d87-a3cc-9b0f7350b2f3
Location
MLS
2019 Market St, St. Louis, MO
Phone: (314) 511-2294
Email: carolyn.kindlebetz@ehi.com
2019 Market St, St. Louis, MO
Phone: (314) 511-2294
Email: carolyn.kindlebetz@ehi.com
Owner
Attn: Carolyn Kindle Betz
TKFC LC
PO Box 16620, St. Louis, MO 63105
Phone: (314) 511-2294
Email: carolyn.kindlebetz@ehi.com
TKFC LC
PO Box 16620, St. Louis, MO 63105
Phone: (314) 511-2294
Email: carolyn.kindlebetz@ehi.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | Yes | No | Emergency communications loss monitor shall work. | 2/22/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work. Voice does not work but video/text works. | 2/22/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.7.2 Seizing of Rope Ends | No | No | 2.20.9.7.2 - Suspension rope tail ends shall be properly seized/banded. They are currently wrapped in electrical tape. | 9/12/2024 |
| A17.1-2016 : Elevators | 3.22 - Wire rope fastening and hitch plate | 2.20.9.5 Wedge Rope Sockets | No | No | 2.20.9.5.4 - Hoist rope tail retaining clips shall be properly spaced. | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track (multiple floors). | 9/12/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop light does not work. | 9/12/2024 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Take corrective action and re-test. | 12/8/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.10.2.2.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually | |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | Counterweight runby does not meet Code Minimum of 6". | |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.11.2.1.2(g) | No | No | Non-elevator related items shall not be stored in Machine Room | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | MCP - Fire Service must be tested and properly documented monthly on Log Sheet |