Inspection
Inspection Details
Equipment ID
11121
11121
Inspection Date
8/15/2022
8/15/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
490303bd-3b3b-427b-b7d2-4887fc24120e
490303bd-3b3b-427b-b7d2-4887fc24120e
Location
Fox Theater
527 N Grand Blvd, St. Louis, MO
Phone: (314) 534-1678
527 N Grand Blvd, St. Louis, MO
Phone: (314) 534-1678
Owner
Attn: Fox Associates
Fox Associates
527 N Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Fox Associates
527 N Grand Blvd, St. Louis, MO 63103
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Machine room shall not be used for storage. | 3/10/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing COP lock. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Non-elevator related wiring shall be relocated and enclosed to conform to NFPA70/NEC. Tele-communication wiring is draped across the machine room, not enclosed, and creating fire penetrations through walls. | 3/1/2026 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an unsealed overspeed valve. The overspeed valve shall be tested with the rated load on for before the next annual inspection. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 3/1/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Sprinkler riser shall not run the entire hoistway, 3 floors. Customer may apply for a variance. | 3/1/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Sump pump discharge pipe runs across elevator machine room close to pump unit and over disconnects; discharge pipe shall be guttered. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | No | No | Non-elevator related wiring shall be relocated and enclosed to conform to NFPA70/NEC. Tele-communication wiring is draped across the machine room, not enclosed, and creating fire penetrations through walls. | 3/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car Operating Panel (COP) lock needs replaced. |