Inspection
Inspection Details
Equipment ID
14089
14089
Inspection Date
8/30/2018
8/30/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
Governor Rope Pull
120/575
120/575
Door Closing Force
NA
NA
External ID
dc857611-00a0-4a52-8fed-1bb3297e611e
dc857611-00a0-4a52-8fed-1bb3297e611e
Location
Homer Phillips
2601 WHITTIER ST, SAINT LOUIS, MO
2601 WHITTIER ST, SAINT LOUIS, MO
Owner
Dominion Services Inc
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
Billing
Attn: Homer Philliips Dignity House II
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | n/a | Maintain machine room lighting three out of four bulbs out | 2/13/2020 | ||
conversion | conversion | n/a | Pit light inopeartive | 2/13/2020 | ||
A17.1-1996 : Elevators | 2.15 - Static control | 1001.2(b)(13) | x | Elevator failed static 125% test. Brake did not hold. Elevator red-tagged. | 10/29/2018 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/13/2020 | ||
A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | Worm gear is leaking excessively on car top and in the cab. | 2/13/2020 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | x | Water in the pit. | 5/13/2020 | |
A17.1-1996 : Elevators | 2.19 - Gears, bearings, and flexible couplings | 1001.2(b)(17) - no reinspect | Worm shaft seal on drive machine worn and leaking. Repair/replace as needed. | 2/11/2021 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 2/25/2021 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate. | 2/11/2021 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide on-site maintenance control program. | 11/15/2021 | ||
A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | x | Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. | 11/15/2021 | |
A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | Clean oil from car top, fan and ceiling/fixtures. | 11/15/2021 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean pit. | 11/15/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Sheave seal worn and leaking, repair as needed. Clean up oil. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Hoistway door closer is missing retainer clip for rod, replace. | |||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Smoke detector in pit has been removed, determine cause. Replace. | ||
MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | Heat detector head in pit has been removed. Determine cause, replace. |