Inspection
Inspection Details
Equipment ID
1141
1141
Inspection Date
8/17/2022
8/17/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Kurt Warttig
Kurt Warttig
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
28
28
External ID
53f9feb7-bc49-4ac1-a5e9-40126c5f8ec2
53f9feb7-bc49-4ac1-a5e9-40126c5f8ec2
Location
Visco Properies, LLC
10296 Big Bend Rd, St. Louis, MO
Phone: (314) 605-8530
10296 Big Bend Rd, St. Louis, MO
Phone: (314) 605-8530
Owner
Attn: c/o Cozad Property Management Co.
Visco Properties LLC
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 781-1890
Email: ltocco@cozadgroup.com
Visco Properties LLC
16 Sunnen Dr, Ste 164, St. Louis, MO 63143
Phone: (314) 781-1890
Email: ltocco@cozadgroup.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperative | 10/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 3.18 | No | No | Twin post Jacks making excessive noise in the down direction. Determine cause and repair. | 10/11/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit stopped working. Provide Relief pressure, record. Check packing for leaks. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of emergency lights and bell. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of phone. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of Phase I operations, record results. | 9/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of Phase II operations, record results. | 9/12/2023 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV in the pit is due for testing, provide. | 8/19/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone inoperable | 12/15/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to perform stop ring pressure test | 12/15/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone. | 12/5/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit to work properly. | 12/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Need to repair door closed button or replace same |