Inspection
Inspection Details
Equipment ID
12528
12528
Inspection Date
8/28/2018
8/28/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
9
9
Governor Rope Pull
100/540
100/540
Door Closing Force
28
28
External ID
202a530a-ef35-4dfa-b0eb-3c7100654964
202a530a-ef35-4dfa-b0eb-3c7100654964
Location
Homer Phillips
2601 WHITTIER ST, SAINT LOUIS, MO
2601 WHITTIER ST, SAINT LOUIS, MO
Owner
Dominion Services Inc
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
Billing
Attn: Homer Philliips Dignity House II
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Repair inoperable emergency light. Reinspect. | 2/11/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency lights shall work. | 2/11/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/25/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate. | 2/11/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 11/15/2021 |
| A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | Yes | No | Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. | 11/15/2021 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean oil from car top, fan and ceiling/fixtures. | 11/15/2021 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit. | 11/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Sheave seal worn and leaking, repair as needed. Clean up oil. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Thrust bearing seal worn and leaking, repair as needed. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light housing has rusted away, replace/ repair as needed . Light is laying in pit floor.but works. |