Inspection
Inspection Details
Equipment ID
25250
25250
Inspection Date
8/11/2022
8/11/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
Freight
Freight
External ID
e30b2b7a-be07-4d13-8d08-121e543f1305
e30b2b7a-be07-4d13-8d08-121e543f1305
Location
Cape Stovall LLC
2216 N Broadway, St. Louis, MO
Phone: (000) 000-0000
2216 N Broadway, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Scott Chapman
Cape Stovall LLC
2216 N Broadway, St. Louis, MO 63102
Phone: (314) 560-9904
Email: scott.chapman@tciproducts.com
Cape Stovall LLC
2216 N Broadway, St. Louis, MO 63102
Phone: (314) 560-9904
Email: scott.chapman@tciproducts.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Car unable to run with a full load. Elevator Red Tagged. | 10/15/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | The car safeties shall be tested with a full load in the car. - Unit Red Tagged | 10/15/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | The 6th floor lentil shall be repaired. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A ladder or steps shall be provided to enter the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car gate is missing the counterweight rope. | 10/15/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | The machine room lighting is insufficient. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Elevator cab shall be enclosed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 2nd floor hall and car button is missing. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Pull box cover is missing and shall be replaced. | 10/15/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Permanent pit lighting shall be provided. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Covers are missing at several places places throughout the hoistway. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be cleaned. | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | There is exposed wires throughout the hoistway. All wiring shall be enclosed in conduit of metal raceway. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | A cover for the bottom of the controller is missing. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car gates have broken slats and broken base and shall be replaced. | 10/15/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car gate is missing the counterweight rope. | 8/11/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Pull box cover is missing and shall be replaced. | 8/11/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Car gates have broken slats and broken base and shall be replaced. | 8/11/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency alarm bell shall be operational. | 4/11/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent ladder or staircase is required for access to the machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Alarm bell shall work with loss of main 120v power. (2nd Notice) | 6/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Bottom limit switch shall work. | 6/26/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| MO Minimum : Elevators | (I) - Pits | (I)7 | Yes | No | Install emergency stop switch in pit. | 4/11/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | All electrical wiring in the hoistway shall be enclosed in metal conduit, flexible conduit or metal raceway or be in compliance with NFPA 70. Conduit and 4x4 box on wall in pit that lower limit switches are being fed from is extremely rusted and deterioration has left wiring exposed and flexible conduit to limit switches without support. Parts shall be replaced to make it compliant. | 4/11/2025 |