Inspection
Inspection Details
Equipment ID
13321
13321
Inspection Date
8/30/2018
8/30/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Thomas Droege
Thomas Droege
Relief Valve Pressure
Slide
9
9
Governor Rope Pull
110/445
110/445
Door Closing Force
26
26
External ID
c7cda1da-b452-4da7-8be7-c5b76b8eafd4
c7cda1da-b452-4da7-8be7-c5b76b8eafd4
Location
Homer Phillips
2601 WHITTIER ST, SAINT LOUIS, MO
2601 WHITTIER ST, SAINT LOUIS, MO
Owner
Dominion Services Inc
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
2355 POLARIS LN N STE 100, PLYMOUTH, MN 55447-4777
Billing
Attn: Homer Philliips Dignity House II
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
2601 WHITTIER ST, SAINT LOUIS, MO 63113-2957
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Phase Ii does not work | 8/30/2018 | |
conversion | conversion | conversion - reinspect | x | Phase I light and buzzer not working | 8/30/2018 | |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | x | x | Repair firefighters service phase II so that it operates as intended. Hold does not work. Did not red tag unit. Reinspect only. | 8/2/2019 |
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) - | Fireman's light and audible needs to work. | 5/13/2020 | ||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)(12) | x | x | Phase 2 is not working, hold does not work, fireman's in car light and buzzer not working. Must be repaired within 30 days, reinspected by October 9th or unit will be red tagged. | 10/13/2020 |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not have 2-way communication. | 10/13/2020 | |
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Maintenance control program shall include current records of maintenance performed. | 10/23/2020 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide on-site maintenance control program. | 2/11/2021 | ||
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide on-site maintenance control records. | 11/15/2021 | ||
A17.1-1996 : Elevators | 2.18 - Traction drive machines | 1001.2(b)(16) | x | Drive sheave seals and worm shaft seals are worn and leaking. Repair as needed. | 11/15/2021 | |
A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | Clean oil from car top, including car fan and ceiling fixtures. | 11/15/2021 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Clean pit. | 11/15/2021 | ||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency lights and alarm bell do not work. | 11/15/2021 | |
A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 1001.2(a)(18) | x | Repair door detector, currently working off light/bell 110V circuit. When power is removed, it does not work. | 11/15/2021 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Provide existing phone to work, pushing button = nothing. |