Inspection
Inspection Details
Equipment ID
11755
11755
Inspection Date
8/9/2022
8/9/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
16/17
16/17
External ID
72b2f005-f0ce-41fd-9aaa-ae35ef6fc9a2
72b2f005-f0ce-41fd-9aaa-ae35ef6fc9a2
Location
Racquet Club
476 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 361-2100
476 N Kingshighway Blvd, St. Louis, MO
Phone: (314) 361-2100
Owner
Attn: Racquet Club
Racquet Club
476 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Frank@rcstl.com
Racquet Club
476 N Kingshighway Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: Frank@rcstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Machine room door shall be self-locking and self-closing. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | Seal the penetrations in the hoistway. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The front and rear door restrictors shall be operational. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Repair the plumbing problem in the machine room. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | The existing pipes in the machine room need to be enclosed in a 2 hour fire rated material. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Yes | No | At the top and bottom landings, the car doors shall clear the hoistway wall when fully open and operated on hoistway access. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Smooth out the machine room floor. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | Yes | No | Flashing fire hat does not flash when required and shall be repaired. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Yes | No | Provide an ABC type fire extinguisher in the machine room. | 8/14/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | Yes | No | Secure the old machine room door on the roof to prevent from opened. | 8/14/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The pipes in the machine room shall be guarded or guttered to prevent leakage onto elevator equipment. | 9/13/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Repair the tripping hazard located in front of the controller. | 9/13/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The rear doors shall be restricted when the car is outside the unlocking zone. | 3/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 8.11.2.1.3(g) | Yes | No | 8.11.3.1.5(e) - The virtual down directional limit shall stop the car before landing on the buffer. | 3/30/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(c) | No | No | Receptacle in machine room shall be a GFCI. | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | The pit shall be kept clean and dry. Remove the water from the pit. | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the elevator machine room. | 9/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door lock needs to be adjusted to properly lock. | 9/21/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/15/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall be operational. | 9/15/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking and operable from the interior space without the use of a key. | 9/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 8/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean and dry. Remove water from the pit. | 7/31/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is due for category 5 testing. | 10/2/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/31/2025 |