Inspection
Inspection Details
Equipment ID
3356
3356
Inspection Date
8/9/2022
8/9/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
99caebba-23f9-41e1-a3fe-4db151a69dfa
99caebba-23f9-41e1-a3fe-4db151a69dfa
Location
Pillsbury Music Building
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
500 COLLEGE HL, LIBERTY, MO
Phone: (816) 781-7700
Owner
Attn: Stephany Guest
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
William Jewel College
500 College Hl #1110, Liberty, MO 64068
Phone: (816) 415-5929
Alt Phone: (816) 536-8036
Email: sguest@william.jewell.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Post emergency evacuation of passengers form inside machine room | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove flammable rags from machine room floor. | 8/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove hydraulic oil from pit floor | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remove spare parts for the elevator from the controller. The controller cabinet is not a storage container. | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door lock needs to be self-locking and non-defeatable. | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Spare parts can not be stored inside elevator controller. | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP on site | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove rags from machine floor | 8/11/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams | No | No | Remove spare parts from the controller cabinet. Controller cabinet is not a storage container | 8/11/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work | 8/11/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 8/11/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide a self locking door knob for machine room door. | 8/11/2026 |