Inspection
Inspection Details
Equipment ID
14386
14386
Inspection Date
7/5/2022
7/5/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
TBD
TBD
Governor Rope Pull
120/730
120/730
Door Closing Force
20
20
External ID
18408e92-cbea-4f17-ac84-077bcb8de1a0
18408e92-cbea-4f17-ac84-077bcb8de1a0
Location
Senate Apartments
265 Union Blvd, St. Louis, MO
Phone: (314) 367-7900
265 Union Blvd, St. Louis, MO
Phone: (314) 367-7900
Owner
Attn: Larry McFadden
275 on the Park
275 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
275 on the Park
275 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Attn: 275 on the Park
275 on the Park - Annex Building
275 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
275 on the Park - Annex Building
275 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | In cab emergency telephone shall work. | 10/18/2018 | |
| conversion | conversion | conversion - reinspect | x | Car top emergency exit must be secured to car top and shall only be able to open from the car top without the use of tools. | 10/18/2018 | |
| conversion | conversion | conversion - reinspect | x | Car door restrictor shall work. | 10/18/2018 | |
| A17.1-1996 : Elevators | 3.8 - Top emergency exit | 1001.2(c)(12) | Car top exit shall be properly secured. | |||
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | Provide code compliant machine room door handle and lock. | |||
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | An ABC type fire extinguisher shall be kept in the machine room. | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display the current state operating certificate. | |||
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 1001.2(b)(8) | All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered. | |||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit lighting shall be operational. | |||
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | x | The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action. | 7/5/2022 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | |||
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | The car door restrictor shall be operational. | 7/5/2022 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/5/2022 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | The category 5 test is incomplete. The following testing item remains: The safeties shall be set with a full load and a slide measurement shall be provided. | 7/5/2022 | |
| A17.1-1996 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 1002.3f | x | The elevator makes contact with the with the car buffer every time the car reaches the bottom landing. Take corrective action. (Prior inspection violation that has yet to be cleared). | 10/26/2023 | |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | x | The car door restrictor shall be operational. (Prior inspection violation that has yet to be cleared). | 10/26/2023 | |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.2 | Condensation is dripping on duct. All pipes conveying liquid, vapor, or gas that are above or come near elevator equipment shall be guarded or guttered. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Could not test wind-up safeties. A tool to reset the car safeties shall be available on-site and the safeties shall be tested. | 10/26/2023 | |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | 110V disconnect shall be labeled. Where there is more than one machine in a room, the disconnect for each machine shall be conspicuously numbered to correspond to the machine it controls. | |||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Category 5 test is still incomplete. All parts of the category 5 test remain except the governor pullout/pullthru and governor switch/jaw. | 10/26/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Inspection is still incomplete. Still need to check pit, restrictor, and SOS. | 10/26/2023 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Acceptance test incomplete. Remaining items: measure slide, 100% car buffer, 0% CW buffer, emergency light/alarm/phone, door pressure, phase 1 & 2 fire service, in-car stop, communication loss, runby measurement, traction loss detection. | 11/2/2023 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Check machine room for adequate lighting (not less than 19 fc at floor). | 11/2/2023 | |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | x | Machine room heat detectors failed to initiate recall or shunt (4 devices). | 11/2/2023 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Two-way communication device shall work. The button lights up, but does not dial (communication loss works). | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | x | 2.24.8.4 - Emergency brake release module shall work and be retested. | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Pit shall be kept clean. Remove excess debris. |