MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in oil and water. The elevator pit shall be kept clean and dry. A sump pump may need to be added to prevent the accumulation of water.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Maintenance, Repair and Replacements - 8.6.5.5.2 Oil Leakage Collection - There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the hydraulic cylinder assembly can be repaired or replaced. Remove the recovery unit after the hydraulic cylinder assembly has been repaired or replaced and record the oil loss per A17.1 2016 - 8.6.5.5.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Water has contaminated the hydraulic control system of the elevator. To prevent further damage to the hydraulic control system and for the safety of the public the elevator was placed out of service. The hydraulic oil shall be replaced and the cause of the contamination shall be corrected. Reinspection shall be performed before the elevator can be returned to service.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The elevator pit floor is covered in oil and water. The elevator pit shall be kept clean and dry. A sump pump shall be added to prevent the accumulation of water. The sump pump shall comply with all state and county requirements.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
A door retaining gib is missing on the 4th floor landing and shall be replaced.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
The pit light fixtures failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.
|
9/17/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Elevator cab alarm bell does not work properly (erratic ringing) needs repaired. Re-inspection required
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Test elevator for operation on emergency power. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
A door retaining gibb is missing on the 4th floor landing and shall be replaced.
|
|