Inspection
Inspection Details
Equipment ID
6541
6541
Inspection Date
8/25/2022
8/25/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Marcus Geno
Marcus Geno
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
11/13
11/13
External ID
d889686a-79e0-4694-881e-d4544f8b1638
d889686a-79e0-4694-881e-d4544f8b1638
Location
SSM St. Marys Health Center- STL
6420 Clayton Rd, Richmond Heights, MO
Phone: (314) 768-8949
Email: david.craft@ssmhealth.com
6420 Clayton Rd, Richmond Heights, MO
Phone: (314) 768-8949
Email: david.craft@ssmhealth.com
Owner
Attn: Madison Himelright
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 768-8949
Email: madison.himelright@ssmhealth.com
SSM Health- ESEP Department
1015 Corporate Square, Ste 160, St. Louis, MO 63132
Phone: (314) 768-8949
Email: madison.himelright@ssmhealth.com
Billing
Attn: David Craft
SSM St. Marys Health Center- STL
6420 Clayton Rd, Richmond, MO 63117
Phone: (314) 768-8949
Email: david.craft@ssmhealth.com
SSM St. Marys Health Center- STL
6420 Clayton Rd, Richmond, MO 63117
Phone: (314) 768-8949
Email: david.craft@ssmhealth.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. | 10/31/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | When testing the audible signaling device (alarm bell) with the 110V disconnect in the machine room in the “off” position, the device failed to sound, indicating that the back-up power device (battery) has failed. Repair for proper operation. | 9/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 9/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean debris from elevator car top | 12/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean trash from elevator pit | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 12/9/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test elevator for operation on emergency power. Re-inspection required | 12/9/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 12/9/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean debris from elevator car top | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to clean trash from elevator pit | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit |