Inspection
Inspection Details
Equipment ID
12485
12485
Inspection Date
8/31/2022
8/31/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Michael Vantassel
Michael Vantassel
Relief Valve Pressure
310
310
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
624dbabc-f9ee-4779-be63-e29dd846d70d
624dbabc-f9ee-4779-be63-e29dd846d70d
Location
Villa Dorado Condo
11741 Casa Grande Dr, St. Louis, MO
Phone: (636) 733-9021
11741 Casa Grande Dr, St. Louis, MO
Phone: (636) 733-9021
Owner
Attn: Grier
Grier Management Group
1400 Elbridge Payne Rd, Ste 210, Chesterfield, MO 63017
Phone: (636) 733-9021
Email: accounting@griergroupinc.com
Grier Management Group
1400 Elbridge Payne Rd, Ste 210, Chesterfield, MO 63017
Phone: (636) 733-9021
Email: accounting@griergroupinc.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emergency phone shall work. | 9/21/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self closing and lockable. | 8/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, needs replaced or have serviced | 8/4/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work on auxiliary power or provide location, needs to be upgraded to do so. Re-inspection required | 8/17/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Provide machine room door to be self closing and self locking. | 8/4/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/4/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone works, unable to communicate and needs to be reprogrammed (bad number). | 8/25/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two way phone goes to automated message prompting to dial a key | 8/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room expired 2023. Fire extinguisher shall be kept up to date yearly | 8/4/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self closing and lockable. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired, needs replaced or have serviced |