Inspection
Inspection Details
Equipment ID
12891
12891
Inspection Date
9/7/2022
9/7/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Rodney Clay
Rodney Clay
Relief Valve Pressure
Slide
00
00
Governor Rope Pull
000
000
Door Closing Force
18
18
External ID
7a102eb7-e32a-4b50-8f39-814d9fbc9ce6
7a102eb7-e32a-4b50-8f39-814d9fbc9ce6
Location
Independence Tower Apartments
728 N Jennings Rd, Independence, MO
Phone: (816) 257-1400
728 N Jennings Rd, Independence, MO
Phone: (816) 257-1400
Owner
Independence Tower Apartments
728 N JENNINGS RD, INDEPENDENCE, MO 64056-1869
728 N JENNINGS RD, INDEPENDENCE, MO 64056-1869
Billing
Attn: Independence Tower Apartments
728 N JENNINGS RD, INDEPENDENCE, MO 64056-1869
728 N JENNINGS RD, INDEPENDENCE, MO 64056-1869
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Emg. phone not working | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | runby less than 2 ins. need to shorten cables | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car top oily an dirty an shall not be used for storage | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Water an oil shall not be allowed to accumulate on pit floor pit has a lot of trash in it. | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | No data tags on Hoist ropes | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car door restrictor not working. | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Missing fire hat covers in car an at hall sta. | 8/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | No gov. rope tags | 8/20/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | fire hat jewell missing | 11/18/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | runby less than 6 ins cant reach final limit need to shorten ropes | 9/7/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | pit has standing water an trash | 11/18/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.27 - Crosshead data plate | 2.20.2 | No | No | no rope data tage | 11/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Provide working 2 way communication | 9/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Shorten ropes to allow unit to activate final | 9/7/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)9 Capacity Plate | No | No | Provide capacity plate for car | 9/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Provide emergency light and bell | 9/7/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Provide rope data tag | 9/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Provide rope data tags. | 11/1/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | REMOVE TRASH AND DEBRIS FROM PIT | 11/1/2024 |