Inspection
Inspection Details
Equipment ID
15707
15707
Inspection Date
7/9/2018
7/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
d81f59fa-afb3-4966-bf9c-292bd94205b8
d81f59fa-afb3-4966-bf9c-292bd94205b8
Location
MetroLink- 8th & Pine
323 S 8TH ST, SAINT LOUIS, MO
323 S 8TH ST, SAINT LOUIS, MO
Owner
Metro Accounts Payable
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Billing
Attn: Metro Accounts Payable
PO BOX 1349, SAINT LOUIS, MO 63188-1349
PO BOX 1349, SAINT LOUIS, MO 63188-1349
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need "Low Overhead" clearly posted in hoistway | 12/14/2018 |
| conversion | conversion | n/a | No | No | Post MO State operating permit in machine room | 12/14/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Cab ventilation not working. | 9/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 6/15/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall not be used for storage of non-elevator equipment. | 9/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | AC unit cannot be located directly over the pump unit in the elevator machine room. Move AC unit | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Condensation line cannot be mounted over the pump unit in the elevator machine room. Move line | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.19 - Guide rails fastening and equipment | 8.11.2.1.3(y) | No | No | Slide guides on the car top have excessive play and lateral movement. Adjust, replace, or repair slide guides | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | No | No | Repair leaking victaulic pipe fitting inside the pump unit in the maching room. | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 8.11.2.1.5(f) | No | No | Both traveling cables are rubbing conduit in the hoistway. Move cables to prevent damage | 10/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Car light disconnect is located 9 feet up. Lower disconnect to where it is accessible | 11/9/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.5 - Traveling cables | 2.8.1 | No | No | Both traveling cables are rubbing conduit in elevator hoistway. Move cables to prevent further damage | 10/29/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | Air conditioning systems shall not be located directly over elevator equipment. | 9/8/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Safety retainers are missing on top and bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |