Inspection
Inspection Details
Equipment ID
13727
13727
Inspection Date
9/2/2022
9/2/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
12857da9-9a66-43c6-9dd4-85636e18cfc9
12857da9-9a66-43c6-9dd4-85636e18cfc9
Location
AT & T - One Bell Center
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
1010 Pine St, St. Louis, MO
Phone: (314) 396-3759
Owner
Attn: Kenneth Gerry
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@att.com
AT&T
1010 Pine Street, St Louis, MO 63101
Phone: (314) 396-3759
Email: kg233j@att.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | Provide Emergency Phone | 3/29/2019 | |
A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | x | Interlock cover on the 17th floor missing. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 7/27/2020 | |
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 2/24/2021 | |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | x | Overspeed governor rope tension sheave is bottomed out. Shorten governor rope. Red tagged. | 2/24/2021 |
A17.1-1996 : Elevators | 1.3 - Operating control devices | 1001.2(a)(3) | Replace missing door close button tactile plate in car operating panel. | |||
A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone does not work. | 9/2/2022 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | Replace missing tactile plate on COP | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Replace CO2 fire extinguishers with ABC type. Both elevator machine room and secondary spaces. | |||
A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | x | Provide existing emergency lights and bell to work. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Replace missing pull straps (3), floors 2B,S,1.. hoistway doors. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | x | Provide testing of the elevator on emergency power. | ||
A17.1-1996 : Elevators | 4.12 - Standby power selection switch | 1001.2(d)(12) | x | Provide testing of the elevator emergency power selector switch (fire command room). |