Inspection
Inspection Details
Equipment ID
3511
3511
Inspection Date
7/19/2022
7/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Bruce Dorsey
Bruce Dorsey
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
16F
16F
External ID
8f6e0f9f-4264-490f-817a-f92630c17558
8f6e0f9f-4264-490f-817a-f92630c17558
Location
Nowlin Middle School
2800 S Hardy Ave, Independence, MO
Phone: (816) 521-5380
2800 S Hardy Ave, Independence, MO
Phone: (816) 521-5380
Owner
Attn: Sarah Barker
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: SARAH_BARKER@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: SARAH_BARKER@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | x | x | the fire service phase 1 keyswitch did not work, repair the keyswitch | 3/12/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | provide a record of findings for firefighters' service operation | 12/15/2020 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/26/2022 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | the monthly firefighters service test log is not being filled out monthly | 1/26/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | the fire service relays in the machine room are hanging by their wires out of the electrical box, relays need to be properly secured to the electrical box | 1/26/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | the fire hat jewel in the car operating panel did not light during phase 1 recall. | 1/26/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) | phase 1 fire service recall audible signal did not work | 1/26/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | label controller, tank, disconnects, car operating panel, pit and car top Elevator #3 | 1/26/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | does not have Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | emergency light battery is weak, the lights dim when the alarm button is pushed, the battery needs to be replaced | 8/23/2023 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | the monthly fire service test log in the machine room is not being filled out monthly | 10/27/2025 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | Replace burnt out cab ceiling lights, required to have 5 foot candles of illumination inside the elevator and minimum of two bulbs | 10/27/2025 | ||
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | Put new bulb in car top fixture and it didn’t work, repair car top work light fixture |