Inspection
Inspection Details
Equipment ID
2072
2072
Inspection Date
9/13/2022
9/13/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jason Stout
Jason Stout
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
f2d8eb6b-5d17-408b-bb9c-555da33e1d5d
f2d8eb6b-5d17-408b-bb9c-555da33e1d5d
Location
Hillyard Industries
402 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 233-1321
402 N 3RD ST, SAINT JOSEPH, MO
Phone: (816) 233-1321
Owner
Attn: Hillyard Industries
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Hillyard Industries
402 N 3rd St, St. Joseph, MO 64501
Phone: (000) 000-0000
Billing
Attn: Hillyard Industries
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Hillyard Industries
PO Box 909, St. Joseph, MO 64502
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Need to post "C-1 Loading No Passengers" sign inside elevator. | 10/3/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Elevator will not operate on fire service phase 2 operation. | 10/24/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light and bell do not operate. | 1/30/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Front and rear car gate reversing edges do not reopen gates. Car gate components need to be maintained for proper operation. | 1/30/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Need to post "C-1 Loading No Passengers" sign inside elevator. Lettering to be at least 1/2 inch high. | 10/3/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Elevator will not operate on fire service phase 2 operation. | 1/30/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency light and bell do not operate. | 9/2/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Front and rear car gate reversing edges do not reopen gates. | 9/23/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Remove spilled oil from top of car canopy | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Post emergency evacuation of passengers form inside machine room | 10/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate inside machine room | 10/3/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 10/3/2025 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Post "C-1 LOADING NO PASSENGERS" sign inside elevator. | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris from pit. | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Front and rear car gate reversing edges do not reopen the gates. | 9/13/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly. | 10/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room. | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Front and rear car gate reversal devices do not reopen the gate. | 9/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan in the machine room | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance record log in the machine room | 10/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State certificate not displayed in machine room | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No MCP | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 10/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 10/3/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lighting not working properly. | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit, remove. | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light not working. | 10/3/2025 |